Xylem HYDROVAR Smart User Manual
Page 38

38
7.29.2 Delay Time
DELAY TIME
2 Sec
Adjustable between 0...100 Sec.
Delayed switch-off of the Hydrovar-Smart
in case of low water, (terminals X1/6-X1/7 opened) and also for the conveyor limit.
Press ¾ on the Hydrovar-Smart to change to
7.29.3 Automatic Error reset
ERROR – RESET
OFF
The parameter can be set OFF (no automatic reset)
or, if you want to have an automatic error reset for
5 times, a delay time of the automatic restart (0-250 sec.) has to be set.
e.g. ERROR-RESET = 5 seconds
The Inverter tries to reset the failure for 5 times, between each try to reset the failure and
restart the HYDROVAR-Smart there is a delay of 5 seconds. After 5 not successful restarts,
the Hydrovar-Smart will shut off and an error message is shown.
The last five error signals are always stored in the Error memory 1 to 5 (main menu)
Press ¾ on the Hydrovar-Smart to change to
7.29.4 Erase Error memory
CLEAR ERRORS
0000
The error memory can be deleted by entering a
password. If you want to know that, please contact
your responsible distributor!
To leave the submenu press the ¾ longer than 3 sec. to change to
S U B ME N U
ERRORS
Press ¾ on the Hydrovar-Smart to change to
7.30 Operating Hours
OPPERATING HOURS
OOOO h.
operating time of the control unit (Hydrovar-Smart
-supply is OK)
Reset by simultaneously pressing of П + Р
until TIMER – RESET appears.
Press ¾ on the Hydrovar-Smart to change to