7.29.2 Delay Time

DELAY TIME

2 Sec

Adjustable between 0...100 Sec.

Delayed switch-off of the Hydrovar-Smart

in case of low water, (terminals X1/6-X1/7 opened) and also for the conveyor limit.

Press ¾ on the Hydrovar-Smart to change to

7.29.3 Automatic Error reset

ERROR – RESET

OFF

The parameter can be set OFF (no automatic reset)
or, if you want to have an automatic error reset for

5 times, a delay time of the automatic restart (0-250 sec.) has to be set.

e.g. ERROR-RESET = 5 seconds
The Inverter tries to reset the failure for 5 times, between each try to reset the failure and
restart the HYDROVAR-Smart there is a delay of 5 seconds. After 5 not successful restarts,
the Hydrovar-Smart will shut off and an error message is shown.

The last five error signals are always stored in the Error memory 1 to 5 (main menu)

Press ¾ on the Hydrovar-Smart to change to

7.29.4 Erase Error memory

CLEAR ERRORS

0000

The error memory can be deleted by entering a
password. If you want to know that, please contact
your responsible distributor!

To leave the submenu press the ¾ longer than 3 sec. to change to

S U B ME N U

ERRORS


Press ¾ on the Hydrovar-Smart to change to

7.30 Operating Hours

OPPERATING HOURS

OOOO h.

operating time of the control unit (Hydrovar-Smart
-supply is OK)

Reset by simultaneously pressing of П + Р

until TIMER – RESET appears.