Federal DOT Regulation 49 CFR Part 192.383, Excess Flow Valve Customer Notifi cation, requires gas
utilities to either voluntarily install Excess Flow Valves (EFVs) on all new home service lines or to notify
builders about EFVs’ benefi ts and availability. EFVs are installed on gas service lines during pre-construction
site work, and automatically activate when a gas line is ruptured. Excess fl ow valves should never be used as
in-line regulators. They cannot perform this function and may damage equipment.

Fig. 1-6, Excess Flow Valve

(above ground ¾" x 4" NPT nipple)

Alpha P/N 042-146-10

1.0

System Overview, continued

1.3 Natural Gas System Block Diagram

For added safety, a low pressure and high pressure excess fl ow valve may be installed.

Do not include the generator system as part of a local gas piping system test. Damage to the
generator pre-regulator may result. The generator system is pressure tested in accordance with
NFPA standards prior to shipment.

Fig. 1-5, Arrangement of Metered, Nominal Pressure (1-2psi) Natural Gas System

NOTE:

ATTENTION:

CAUTION!

S

CONTROL

CONTROLS

ENGINE

Demand

Low-pressure

Regulator

14" WC

(max.)

WC = Water Column H

2

O

Pre-Regulator

Maxitrol 325-3

10 psi max input

Flare Coupling

(Quick-Disconnect)

NOTE: 1 psi = 28" WC

0.5 psi (min.)

1 psi (nominal)

10 psi (max)

Engine must have

7" to 11" WC and 156 cubic

feet/Hr. to operate

Solenoid

APU

Enclosure

Meter

Manual

Shutoff

Low pressure excess

flow valve (optional)

High pressure excess flow valve

(optional)