2 alpha ignition battery charger overview – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual

Page 74

Advertising
background image

74

042-288-B0-001, Rev. A

Fig. 6-2, Wiring for ECM, Ignition Battery Charger, and Ignition Battery

6.0 Operation,

continued

6.2 Alpha Ignition Battery Charger Overview

The Alpha Ignition Battery Charger (Alpha P/N 744-870-21)) keeps the ignition battery
charged to start the Auxiliary Power Unit (APU) in the event of an extended power outage.
The charger is active when the yellow LED on the face of the unit is lit. When the generator
starts, the Alpha Ignition Battery Charger (IBC) shuts off and internal engine charger takes
over ignition battery charging.

48V Systems

The ECM monitors ignition battery voltage via the generator control board. The following
conditions must be met for the ECM to turn on the ignition battery charger:

DC bus greater than 49Vdc

Ambient temperature less than 35°C and battery voltage less than 13.2Vdc, or battery
voltage less than 12.6V at any temperature

The following conditions turn the ignition battery charger off:

Engine off and DC bus less than 48Vdc

Ambient temperature greater than 40°C and battery volts greater than 13.2

Battery volts greater than 14.5

Fig. 6-1, Ignition Battery Charger LED

LED ON Indicates Charger is

Active

Engine

Control

Module

Charger

Control

Ignition

Battery

Charger

Ignition Battery

DC BUS

Charger

Power

PCB Mounted

Temp Sensor

Advertising