8 fuel conversion, natural gas to lp – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual

Page 83

Advertising
background image

042-288-B0-001, Rev. A

83

7.0 Maintenance,

continued

7.8 Fuel Conversion, Natural Gas to LP

7.8.1 PN-6x-T Pre-regulator Removal with Low Pressure Switch Installation

Required Tools:

7/8" open-end wrench

In this procedure, the pre-regulator is removed, and a low pressure switch is installed
in its place. Reverse this procedure if changing from (LP) liquid propane to (NG)
natural gas.

1. Remove the inlet nipple that passes through the enclosure wall.

2. Loosen the quick disconnect fi tting just below the pre-regulator, and remove the

pre-regulator assembly.

3. Do not apply pipe sealant to the Quick Disconnect fi tting. Install the low

pressure assembly onto the Quick Disconnect fi tting and tighten.

4. Reinstall the inlet nipple through the enclosure wall. Connect alarm plug into the

ECM wiring harness.

Fig. 7-8, PN-6x-T Pre-regulator Removal

The following procedure must only be performed by qualifi ed personnel. To prevent
injury, disable generator and disconnect gas supply prior to beginning the gas conversion
procedure.

Quick

Disconnect

Fitting

Fig. 7-9, PN-6x-T Switch Assembly Installed

WARNING!

Advertising
This manual is related to the following products: