042-288-B0-001, Rev. A

89

Fig. 8-1, Gas Hazard Detector Interface Connector

Fig. 8-2, Low Fuel Pressure Interface Connector

Pin Description

Function

1

Gas Hazard Sensor Switch

Active OPEN signal denotes gas hazard (Logic HIGH)

2

Gas Hazard Power/Alarm Common

Return signal path for sensor

3

Gas Hazard Logic Power +12Vdc Fused

Logic Power for Logic PCB & sensor

8.0 Interconnection

8.1 Gas Hazard Alarm Interface Connector

The Gas Hazard Detector Interface Connector is connected between the wire harness and
detector unit as shown. The interface control is a 3-pin (1x3 row) Universal Mini Mate-’N’-Lok
style male connector.

8.2 Low Fuel Pressure Interface Connector

The interface control is a 2 pin Mini Mate-'N’-Lok connector (near gas solenoid):

Pin 1 = +12Vdc activates (opens) solenoid ONLY when APU is running. Controlled by
APU engine ON command

Pin 2 = Low fuel pressure switch (negative)

Pin

Description

Function

1

Low Fuel Pressure Sensor Contact

Closed (LOW signal) denotes Low
Fuel Pressure (LP Versions only)

2

Low Fuel Pressure Common

Return signal path for sensor