62

042-288-B0-001, Rev. A

Major Alarms

Abbreviation

Major

Minor

Notify

Comm

System

1

2

3

4

5

6

7

8

9

LO

OT

OS

OC

GH

WI

PS

LP

OV

Major Alarms

Abbreviation

Major

Minor

Notify

Comm

System

10

11

12

13

14

15

16

17

18

CF

AO

TF

IB

TP

DC

ED

LF

AD

19

SR

Red

Green

Amber

4.0

The Engine Control Module, continued

4.6 ECM

Alarm

Overview

Alarms are indicated in three ways: ECM LEDs, RS-485 communications, and alarm
contact closures on the ECM transponder interface. Alarm indications on the ECM LEDs are
displayed by pressing the service reset button momentarily. Pressing the service reset switch
again will reveal the next alarm in the list. When the alarm list has been exhausted, all LEDs
will fl ash several times and then return to their normal functions. Placing the RAS switch to
the STOP position for three (3) seconds, then switching back to AUTO will clear any
latched alarms and start the generator if the cause of the alarm has been corrected.

The following table shows the LED patterns and the alarms they represent.

1. (LO)* Low Oil Pressure

2. (OT) Engine Over-temp

3.

(OS)* Engine Over-speed

4.

(OC)* Engine Over-crank

5.

(OV)* Alternator Over-voltage

6.

(GH)* Gas Hazard

7. (WI) Water Intrusion

8.

(PS)* Pad Shear

9. (LP)*** Low Fuel Pressure

10. (CF)*** Control Fail

11. (AO)

Alternator

OFF

12. (TF)* Self-Test Fail

13.

(IB) Low Ignition Battery

14. (AD)

Auto-mode

Disabled

15.

(TP) Tamper (Default, Disabled)

16.

(DC) DC Bus fault

17.

(ED) Engine Disable

18.

(LF)** Line Failure

19.

(SR)** Service Required

Legend: * = Latching Alarm

**

= Notifi cations

***

= Alarm “latches” after 5 activations

Table 4-2, Major/Minor Alarm Indications and Notifi cations

(LEDs displayed on the ECM)