6 inverter battery dc sense interface connector, 5 ecm enclosure alarm interface connector – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual

Page 91

Advertising
background image

042-288-B0-001, Rev. A

91

Fig. 8-5, ECM Enclosure Alarm Interface Connector

8.6 Inverter Battery DC Sense Interface Connector

ECM - Inverter Battery DC Sense Interface Connector J8. The interface control is a 3-pin (1x3
row) Mini Mate-’N’-Lok style connector.

Fig. 8-6, Inverter Battery DC Sense Interface Connector

Pin

Description

Function

1

Water Intrusion Sensor

Contact OPEN (HIGH signal) denotes water

2

Water Intrusion Common

Return signal path for sensor

3

Pad Shear Sensor

Contact CLOSED (LOW signal) denotes pad shear

4

Pad Shear Common

Return signal path for sensor

5

Low Fuel Pressure Sensor

Contact CLOSED (LOW signal) denotes low fuel
pressure (LP versions only)

6

Low Fuel Pressure Common

Return signal path for sensor

7

Gas Hazard Sensor Switch

Active OPEN signal denotes gas hazard (Logic HIGH)

8

Gas Hazard Power/Alarm

Return signal path for sensor (Common)

9

Gas Hazard Logic Power

Logic power for Logic PCB & sensor (+12Vdc Fused)

10

Door Open Sensor

Contact CLOSED (LOW signal) denotes door is open

11

Door Open Common

Return signal path for sensor

12

No Connection

13

+12V Fused

Fan

14

Common

Fan

8.0 Interconnection,

continued

8.5 ECM Enclosure Alarm Interface Connector

The Alarm Interface Connector (J10) is connected to the Power PCBA. The interface control
is a 14-pin (2x7 row) Universal Mini Mate-’N’-Lok style male connector.

Pin

Description

Function

1

DC Bus Sense (POS.)

Output inverter battery bus – positive connection, 48 and 98Vdc buses

2

No Connection

3

DC Bus Sense ( NEG.)

Output inverter battery bus – positive connection, 48 and 96Vdc buses