Backfi ll trenches over conduit.

Concrete pad.

Stagger or nest conduits for passage through the
three inch pad sweep opening on CE-3x2.

A

B

C

D

When pouring the pad the sweeps may extend to a
maximum of 4 inches above the fi nished pad to pre-
vent concrete from fi lling the sweep openings. After
the concrete is set, trim the conduit to a height no
more than 2 inches above the surface of the pad.

Fig. 3-3, Cross-section of Sweep Trench

C

B

A

Max. height = 2.00"

D

3.0 Installation,

continued

3.1

Installing the CE-3x2 5K-T or PN-6x-T 7.5kW Pad Template, continued