8 liquid propane utility fuel hookup, ce-3x2 5k-t – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual

Page 45

Advertising
background image

042-288-B0-001, Rev. A

45

3.0 Installation,

continued

3.8 Liquid Propane Utility Fuel Hookup, CE-3x2 5K-T

For collocated propane enclosures, see the CE-G Series Enclosure Installation Manual,
Alpha P/N 031-093-C0-001, located at www.alpha.com.

Connection to the LP fuel line is made using a 3/4" shear point union, 1/2" black iron pipe,
and the appropriate pipe thread sealant suitable for use with propane vapor.

Approved pipe thread sealant must be used on all fuel line connections (except fl are
fi ttings).

Thoroughly check the fuel system for vapor leaks. Use an approved leak detector liquid,
or a soap-water solution, with the fuel system pressurized to the cabinet with 0.5 to 1.0
pounds of fuel pressure. Do not use test solutions that contain ammonia or chlorine,
since they prevent soap from bubbling.

Check and satisfy all local codes before connecting gas to the fuel system.

Observe all safety precautions when working with fuel lines. The illustrations on this page
should be considered for general reference only. Installation should ONLY be done by
qualifi ed personnel. Alpha is not liable for gas leaks resulting from improper installation.

WARNING!

Fig. 3-16, Propane Fuel Hookup, CE-3x2 5K-T

User-provided LP Tank

Manual

Shutoff

Advertising