Calibration Procedure:

1. Set the ECM Run/Auto/Stop (RAS) switch to the STOP position.

2. Remove the Allen-head screw located on the secondary or demand regulator.

3. Open both ports on the DWYER #1212 manometer.

4. Set the scale of “0” between the water lines. Connect the pressure test hose.

5. Remove the Maxitrol regulator adjustment cover (located in the gas service box outside

of the enclosure).

6. Apply 0.5 psi to 2.0 psi gas pressure to the gas package.

7. Place the ECM’s RAS switch in the RUN position. The starter then cranks the engine until

the generator starts (this may take a few seconds to draw excess air from hoses). When
the ECM RAS switch is placed in the RUN position, the ECM starts the engine.

8. Verify the DWYER #1212 manometer reads 5-1/2" above the “0” mark, and 5-1/2" below

the “0” mark. This equals 11" water column of pressure. Adjust the Maxitrol regulator in a
clockwise direction to increase pressure, and in a counterclockwise direction to decrease
pressure.

7.0 Maintenance,

continued

7.9

Maxitrol Pre-regulator Calibration, continued

• No matches or open fl ame or sparks. Use caution whenever working in the area to

prevent possible combustion of fuel vapors.

• Leak Hazard: Use caution whenever working in the area to prevent and correct any

leaks detected.

WARNING!

Fig. 7-16, Manometer Connection

Do not bottom out the regulator adjust screw. If you cannot get a reading, retest the inlet pressure
to the Maxitrol gas package.

CAUTION!

9. Press and hold the ECM’s RAS switch in the STOP position until the generator stops.

10. Disconnect the DWYER #1212 manometer gas pressure test kit from the secondary

demand regulator.

11. Reapply a small amount of an approved pipe sealant to the Allen-head cap screw,

replace and tighten into the demand regulator.

12. Replace the Maxtrol regulator access cap and gasket, and tighten.

Reverse view of demand

regulator showing port

Connect hose and fi tting to the

demand regulator

5 ½"

5 ½"

KEEP PORT OPEN

11"

WATER

COLUMN TOTAL

DWYER

1212

MANOMETER