7.1 Servicing

the

APU

Required Tools and Equipment:

• Phillips screwdriver

10mm socket wrench

3/8" open-end wrench

Digital Voltmeter (DVM) capable of displaying true RMS

Battery operated frequency counter (or DVM with this function)

Prior to Performing Maintenance Activities:

1. For routine engine maintenance procedures, refer to the Kohler Power Systems COM7.5

Operation Manual included with your generator.

2. Notify contact personnel that the unit will be out of service for maintenance.

3. Disable the generator ECM (RAS switch to Stop) to prevent unexpected engine start.

4. Switch the DC Output circuit breaker to the OFF position.

5. Verify the gas sensor has no alarms.

6. Ensure the engine/generator is cool to the touch. Exhaust pipes can cause serious burns.

The following components on the APU are accessible from the front, and do not require
removing the enclosure cover:

Air fi lter replacement

Rectifi er replacement

Oil fi lter

Oil fi ll

Dual fuel load block (propane/natural gas)

Electrical interface connections

Demand regulator pressure tap

The duplex outlet is designed for the carburetor and block heaters
only. This is NOT a service outlet.

Failure to perform recommended maintenance will result in
equipment damage, and may void the equipment warranty.

Failure to use recommended replacement parts or procedures
may result in equipment damage, and may void the equipment
warranty.

A corrosion inhibiting coating (i.e. LPS 3) must be used on all exposed connectors (battery posts, fuse tabs,
etc.) and reapplied annually per the manufacturer’s instructions.

NOTE:

CAUTION!

Avoid exhaust pipes while checking oil. Exhaust pipes can cause serious burns.