8 ecm dip switch and fuse confi guration – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual

Page 64

Advertising
background image

64

042-288-B0-001, Rev. A

4.0

The Engine Control Module, continued

4.8 ECM DIP Switch and Fuse Confi guration

The ECM PCB has an eight-position DIP switch (SW5) used to confi gure the generator
interface, APU output voltage (AC or DC), and utility voltage.

The GRI board has three fuses, F1, F2, and F3.

F2: 12V Output to

APU Fan and Enclosure

Gas Detector

(2A, 250V Slo-Blo)

Alpha P/N 460-205-10

F3: 120/240Vac Input

to ECM Logic Transformer

(250mA, 250V Slo-Blo)

Alpha P/N 460-166-10

SW5

F1: 12V Input from APU

(2.5A, 250V Slo-Blo)

Alpha P/N 460-204-10

GRI

ECM PCB

Fig. 4-5, SW5 and Fuse Locations

Table 4-3, Telecom Defaults

Telecom Defaults

Low DC Bus Level

Default 49V (2V/cell)

High DC Bus Level

Default to 57V (2.38V/cell)

Service Interval

Default 100 hours

Autotest Interval

Will auto set to 14 days when SW5-8 is set ON

Autotest Duration

Default 10 minutes

Start Delay

Default 180 seconds (3 minutes)

Shutdown Delay

Default 720 seconds (12 minutes)

Over-voltage Duration

Default 5 seconds