7.0 Maintenance,

continued

7.9 Maxitrol Pre-regulator Calibration

Required Tools and Materials:

• Flat

Tip

Screwdriver

DWYER # 1212 water column (0-16") gas pressure test kit

Allen head wrench set

NFPA-approved pipe sealant (i.e. Megaloc Multipurpose Thread Sealant)

Leak detector compound (soapy water)

The Maxitrol 325-3 regulator has a maximum inlet pressure of 10 PSI. Alpha Technologies
recommends all installations range between 1-2 PSI for consistent of gas fl ow.

An external water trap must be supplied outside the enclosure in accordance with local, state,
and National Fire Protection Agency (NFPA) codes. Water sent through the gas lines to the
regulator system can damage the secondary demand regulator.

Fig. 7-13, Primary Fuel Regulator

Remove cap to access

adjustment screw

CE-3x2 5K-T

PN-6x-T 7.5kW