0 maintenance, Table 7-1, scheduled maintenance, Maintenance procedures – Alpha Technologies AlphaGen PN-6x-T 7.5kW 48VDC - Technical Manual User Manual

Page 75

Advertising
background image

042-288-B0-001, Rev. A

75

7.0 Maintenance

The engine/alternator requires maintenance at regular intervals to remain reliable and ready to
provide backup power when needed. Please refer to the following table for general maintenance
guidelines. For specifi c recommendations regarding maintenance intervals, please refer to the
supplied engine manufacturer’s operator’s manual.

Maintenance Procedures: X = Action, R = Replace as necessary
Frequency: D = Daily, W = Weekly, M = Monthly, Q = Quarterly, AS = Attended Startup, S = Six Months

Y = Yearly (all numbers in hours)

Table 7-1, Scheduled Maintenance

System Component or

Procedure

Visual Inspection

Verify

Change

Clean

Test

Frequency

FUEL

Inspect flexible lines and

connections

X

R

Q

Check fuel supply

X

W or AS

Inspect fuel piping

X

Y

LUBRICATION

Check oil level

X

X

D, AS

Change oil

R

Y or 100

Replace oil filter

R

Y or 100

COOLING

Verify air ducts, filters, and

free from debris

X

X

Y or AS

EXHAUST SYSTEM

Check for leakage. carbon or

soot residue indicates leaks.

Repair immediately.

X

X

X

Y

Check for fire hazards

X

Y

Check for loose or broken

hangers and supports.

Clean exhaust outlet

X

R

Y or AS

BATTERY CONNECTIONS

Check battery charger

operation, charge rate

X

M

Clean, re-torque battery

terminals

X

X

X

Y or 100

ELECTRICAL SYSTEM

General inspection

X

Q

Inspect cables for abrasion

(Generator compartment)

X

X

S

Reapply corrosion-inhibiting

coating on all exposed

connector assemblies

X

Y

ENGINE & MOUNTING

General insp ection

X

W

Inspect air cleaner element

R

Y or 100

Inspect spark plugs

R

Y or 500

CONTROL SYSTEM

Verify remote control operation

X

M

Run generator set

X

W

GENERATOR SET

Inspect generator set

X

Prestart

Exercise generator set

X

M

GENERAL CONDITION OF

EQUIPMENT

Check for signs of damage due

to vibration, leakage,

excessive noise, extreme

temperature, or deterioration.

X

X

X

W

Inspect and clean cabinet

interior

X

X

Q or AS

Maintenance Procedures

louvers are

Advertising
This manual is related to the following products: