Connection to a boiler (version eh) – DE DIETRICH KALIKO TWH 200E - TWH 300E - TWH 300EH User Manual

Page 30

Advertising
background image

CAUTION

If the mains pipes are made of copper, fit a sleeve made

of steel, cast iron or any other insulating material between

the tank’s hot water outlet and the pipes to prevent

corrosion to the connection.

n Connecting the domestic cold water

Make the connection to the cold water supply according to the

hydraulic installation diagram.

Install a water drain in the boiler room and a funnel-siphon for the

safety unit.
The components used for the connection to the cold water supply

must comply with the prevailing standards and regulations in the

country concerned. Fit a one-way valve to the domestic cold water

circuit.

n Pressure reducer

If the mains pressure exceeds 80% of the calibration of the valve or

safety unit (e.g. 5,5 bar (0,55 MPa) for a safety unit calibrated to 7 bar

(0,7 MPa)), a pressure reducer must be installed upstream of the

appliance. Install the pressure reducer downstream the water meter

in such a way as to ensure the same pressure in all of the installation

pipes.

n Measures to take to prevent hot water flow return

Fit a one-way valve to the domestic cold water circuit.

4.6.2.

Connection to a boiler (Version EH)

CAUTION

Before making the water connections of the heating circuit

and domestic hot water tank heat exchanger, it is

imperative to rinse the circuits to remove any particles

which might damage the components (safety valve,

pumps, valves, ...).

4. Installation

TWH 200E TWH 300E TWH 300EH

28

03/02/2014 - 300026515-001-03