Control system sequence, Return to the factory settings – DE DIETRICH KALIKO TWH 200E - TWH 300E - TWH 300EH User Manual

Page 53

Advertising
background image

Parameters Description

Adjustment range Factory

setting

P 26

Antilegionella function. The tank is overheated every Saturday from 1 o’clock to

6 o’clock (65 °C).

4

0 = Off

4

1 = Activated outside holiday periods

4

2 = Always activated

0 - 1

0

P 27

Compressor cut-off hysteresis in relation to the set point for the bottom domestic

hot water temperature sensor (only in Auto or Boost mode)

5 - 15

10

P 28

Maximum DHW temperature (bottom sensor) for compressor cut-off (°C) (only

in Auto or Boost mode)

35 - 50

45

P 29

Minimum duration of compressor operation (minutes)

3 - 10

3

P 30

Anti-short-cycle period between 2 compressor start-ups (minutes)

5 - 10

5

P 31

Hydraulic additional heating

4

0 = contact R6 closed if there is an additional hydraulic heating request

4

1 = contact R6 opened if there is an additional hydraulic heating request

0 - 1

0

P 32

DHW setpoint used for the antilegionella function

55 to 70 °C

65 °C

5.7.3.

Control system sequence

Control system sequence
Status Sub-status Operation
0

0

Appliance off

7

Compressor post-operation

1

1

Anti-short cycle activated

2

Wait for the start-up condition for domestic hot water production

3

Start-up of the fan and the defrosting valve

2

5

Compressor starts

6

Defrosting

3

1

Anti-short cycle activated

4

Additional heating starts

7

Compressor post-operation

4

5

Compressor starts

6

Defrosting

9

--

Blockage state

5.7.4.

Return to the factory settings

1. Press the ( and ) keys simultaneously for 5 seconds. The

rSt

menu is displayed.

C003495-B

3

1

4

3

4

1

2

MENU

MODE

TWH 200E TWH 300E TWH 300EH

5. Commissioning

03/02/2014 - 300026515-001-03

51