List of the parameters – DE DIETRICH KALIKO TWH 200E - TWH 300E - TWH 300EH User Manual

Page 52

Advertising
background image

5.7.2.

List of the parameters

Parameters Description

Adjustment range Factory

setting

P 01

DHW setpoint in Auto mode

40 to 70 °C

55 °C

P 02

DHW set point in Eco mode

40 to 65 °C

55 °C

P 04

Choice of mode for the DHW Comfort period:

4

0 = Use the time programs.

4

1 = Use the electricity tariff information input. Tells you whether or not

domestic hot water production is permitted (HP1 = not permitted => Contact

closed, HC0 = permitted => Contact open).

4

2 = Use the electricity tariff information input. Tells you whether or not

domestic hot water production is permitted (HP1 = not permitted => Contact

open, HC0 = permitted => Contact closed).

4

3 = Use the time programs. The status of the electricity tariff information

input is used to activate the Boost function with compressor only (HP1 =

Boost deactivated => Contact closed, HC0 = Boost activated => Contact

open).

4

4 = The status of the electricity tariff information input is used to activate

the Boost function with compressor only (HP1 = Boost activated => Contact

open, HC0 = Boost deactivated => Contact closed).

4

5 = The status of the electricity tariff information input is used to activate

the Boost function with compressor and back-up (HP1 = Boost deactivated

=> Contact closed, HC0 = Boost activated => Contact open).

4

6 = The status of the electricity tariff information input is used to activate

the Boost function with compressor and back-up (HP1 = Boost activated

=> Contact open, HC0 = Boost deactivated => Contact closed).

0 - 6

0

P 06

Automatic switch to summer time (last Sunday in March) and winter time (last

Sunday in October):

4

0 = Function not active (for countries where the time change is done on

other dates or is not in use)

4

1 = Function active

0 - 1

1

P 07

DHW setpoint in Boost mode

40 to 70 °C

62 °C

P 17

Protection by impressed current anode

4

0 = Deactivation

4

1 = Activation

0 - 1

1

P 18

Water volume contained in the DHW tank (x 10 l)

6 - 255

27

P 19

Water volume for one bath (l)

10 - 255

120

P 20

Maximum duration of the Boost mode (h)

1 - 10

6

P 21

Measurement unit

4

0 = °C

4

1 = °F

0 - 1

0

P 22

Back-up type

4

0 = None

4

1 = Electrical back-up

4

2 = Hydraulic additional heating

0 - 2

1

P 23

Time delay for starting the electrical or hydraulic back-up in Automatic mode

(Hours)

0 - 10

5

P 24

Compressor start-up time (seconds)

60 - 255

120

P 25

Management of the fans in domestic hot water production mode

4

0 = Automatic

4

1 = Average speed of fan rotation

4

2 = Maximum speed of fan rotation

0 - 2

0

5. Commissioning

TWH 200E TWH 300E TWH 300EH

50

03/02/2014 - 300026515-001-03