4. Connect the 2 wires on the command module.
5. Put the control system module in place.

4.9

Electrical connections

4.9.1.

Recommendations

WARNING

4

Only qualified professionals may carry out electrical

connections, always with the power off.

4

Do not connect the power supply directly to the HP/

HC contact.

The earthing shall comply with local standards.
Power the appliance with a circuit that includes a 16 A omnipolar

circuit breaker, D curve type, with a gap of more than 3 mm.
The DHW tank is delivered with a 3G cable. If the power cable is

damaged, it must be replaced by the manufacturer, its after sales

service or persons with similar qualifications in order to obviate any

danger.

The electricity supply is connected to the mains by connection cable

(~230 V, 50 Hz) and electrical plug.
The HP/HC connection is made on the terminal block.

4.9.2.

Connecting the hydraulic back-up (Version
EH)

1. Remove the front cover.

¼See chapter "Installing the control system in the living

room", page 32

4

5

C003407-D

TWH 200E TWH 300E TWH 300EH

4. Installation

03/02/2014 - 300026515-001-03