22

Conversionofcontrolfunction

Type 2000, 2002, 2012

Remove filler piece

19

with intermediate washer

20

and O-ring

21

(filler piece is not required for CFB).

Insert pressure springs

35

.

Place intermediate washer

20

and lightly lubricated O-ring

21

on spindle.

Insert pistons

22

and supporting washer

24

.

Wet spindle thread

2

with special adhesive LOCTITE 274 and screw on nut

25

.

Mount position indicator

26

.

Insert new O-ring

30

into the groove of the actuator body.

Do not damage sealing edges when replacing the seal!

Replace graphite seal

5

.

only for va body: Lubricate nipple thread

6

with Klüber paste UH1 96-402.

Clamp body

1

.

note!

damage to the seat contour!

▶ During installation, take care that there is no damage to the seat contour.

Observe tightening torques according to “Table 3”.

Screw in nipple

6

with actuator in valve body

1

.

for actuator size G (100 mm) and h (125 mm): Insert washer

40

.

Mount cover

31

and screw tightly with special wrench.

Check the valve for function and leaks.

tightening torques:

material of nipple

thread

diameter

tightening torques

(nm)

Brass or stainless

steel

15

45

20

50

25

60

32

65

40

65

50

70

65

70

Table 3:

Valve body tightening torques