Conversionofcontrolfunction

Type 2000, 2002, 2012

7.3

conversion from control function a (cfa) to
control function i (cfi)

Danger!

danger – high pressure!

▶ Turn off the pressure and vent the lines before loosening lines or valves.

Risk of injury from improper maintenance!

▶ Maintenance may be performed by authorized technicians only!

▶ To screw on or unscrew valve body or actuator, use an open-end wrench, never a pipe wrench.

▶ Observe tightening torques.

Required parts:

item

description

30

1 O-ring

procedure:

Mount valve

1

on the body.

Caution!

danger through taut springs!

▶ Carefully open piston actuator!

Release cover

31

with special wrench until the springs are completely relaxed, holding up the actuator body

12

against the hexagon.

For information about the special wrench, see Chapter “8. Installation tools”.

for actuator size G (100 mm) and h (125 mm): Remove washer

40

.

Remove pressure springs

28

29

.

Insert O-ring

30

into the groove of the actuator body.

Mount cover

31

and screw tightly with special wrench.

Check the valve for function and leaks.

For control function I (CFI) connect both control air connections to the control lines.

english