5 theory of operation – Hach-Lange RTC113 ST-Module User Manual
Page 13

13
General information
Figure 3
Design of the analog and digital input and output modules
Note: The number of LEDs indicates the number of channels.
2.5 Theory of operation
2.5.1
Theory of operation of the RTC Module
The RTC113 RTC Module outputs analog (0/4–20 mA) and digital (0/24 V) signals for the
polymer dosing rate or the feed flow rate of mechanical sludge thickening devices. Digital
fieldbus signals from sc1000 communication cards can also be used.
2.5.2
Input signals
The most important input signals are:
•
Sludge influent TSS concentration (concentration of solids)
•
Feed flow rate of the machine-controlled sludge thickening
•
Thickened sludge TSS concentration (optional)
•
Status of the thickened sludge pump (on/off)
2.5.3
Parameters for configuration
The most important parameters for configuration are:
•
The required specific polymer dosing [g polymer/kg TSS]
•
The target TSS concentration in thickened sludge
Note: In a closed-loop circuit, TSS measurement is required in thickened sludge.