Parameterization and operation

4.7.10 DERIVATIVE TIME TSS

Derivative time for the PID closed-loop controller for the TSS

concentration in the thickened sludge.

4.8 INPUT/OUTPUT LIMITS

4.8.1

FEED FLOW LOW

Feed flow rate input signals below this value [m

3

/h] are set to this

value. This means that very low feed flow rates can be avoided.

4.8.2

FEED FLOW HIGH

Feed flow rate input signals above this value [m

3

/h] are set to this

value. This avoids load peaks.

4.8.3

FEED FLOW SMOOTHING

Feed flow measurement values are smoothed in line with this

parameter.

SMOOTHING = 1: The signal for the flow rate measurement

is not smoothed.
SMOOTHING = 2: Smoothing is performed over 3 minutes.
SMOOTHING = 3: Smoothing is performed over 5 minutes.
SMOOTHING = 5: Smoothing is performed over 12 minutes.
SMOOTHING = 10: Smoothing is performed over

25 minutes.

Example:
With the setting SMOOTHING = 2, it takes 3 minutes for the

smoothed value to reach 95 % of the final value after an abrupt

change in the feed flow rate.

4.8.4

LIMIT TSS IN LOW

TSS measurement values from the influent that are below this

value [g/L] are set to this value (to avoid low peaks).

4.8.5

LIMIT MAX TSS IN HIGH

Measurement values from the influent that are above this value

[g/L] are set to this value (to avoid high peaks).

4.8.6

TSS IN SMOOTHING

TSS measurement values from the influent are smoothed in line

with this parameter.

SMOOTHING = 1: The signal is not smoothed.
SMOOTHING = 2: Smoothing is performed over 3 minutes.
SMOOTHING = 3: Smoothing is performed over 5 minutes.
SMOOTHING = 5: Smoothing is performed over 12 minutes.
SMOOTHING = 10: Smoothing is performed over

25 minutes.