7

Section 1

Technical data

These are subject to change without notice.

Embedded PC (compact industrial PC)

Processor

Pentium

®1

, MMX compatible, 500 MHz clock rate

Flash memory

2 GB compact flash card

Internal working memory

256 MB DDR-RAM (not expandable)

Interfaces

1× RJ 45 (Ethernet), 10/100 Mbit/s

Diagnostic LED

1× power, 1× LAN speed, 1× LAN activity, TC status,

1× flash access

Expansion slot

1× CompactFlash type II slot with ejector mechanism

Clock

Internal, battery-buffered clock for time and date (battery can be

replaced)

Operating system

Microsoft Windows

®2

CE or Microsoft Windows Embedded Standard

Control software

TwinCAT PLC Runtime or TwinCAT NC PTP Runtime

System bus

16 bit ISA (PC/104 standard)

Power supply

Via system bus (through power supply module CX1100-0002)

Max. power loss

6 W (including the system interfaces CX1010-N0xx)

Analog inputs

0/4 to 20 mA for input of the feed flow rate and the polymer flow rate

Number of inputs

One-channel: 2 (KL3011)
Two-channel: 4 (KL3011)

Internal resistance

80 ohm + diode voltage 0.7 V

Signal current

0/4 to 20 mA

Common mode voltage (U

CM

)

35 V max.

Measurement error (for entire measurement

range)

< ± 0.3 % (from end value of measurement range)

Voltage surge resistance

35 V DC

Electrical isolation

500 V

eff

(K-bus/signal voltage)

Digital inputs

Enabling of the open-loop control (thickened sludge pump on/off)

Number of inputs

2 (KL1002)

Nominal voltage

24 V DC (-15 % / +20 %)

Signal voltage "0"

–3 to +5 V

Signal voltage "1"

15 to 30 V

Input filter

30 ms

Input current

5 mA (typ.)

Electrical isolation

500 V

eff

(K-bus/field voltage)