Technical data – Hach-Lange RTC113 ST-Module User Manual

Page 8

Advertising
background image

8

Technical data

Analog outputs

Output of the polymer dosing, output of the feed flow rate

Number of outputs

One-channel: 2 (KL4012)
Two-channel: 4 (KL4012)

Supply voltage

24 V DC via the power contacts
(Alternatively, 15 V DC with bus termination KL9515)

Signal current

0/4 to 20 mA

Working resistance

<500 ohm

Measurement error

± 0.5 LSB linearity error
± 0.5 LSB offset error
± 0.1 % (relative to the measuring range end value)

Resolution

12 bit

Conversion time

Approximately 1.5 ms

Electrical isolation

500 V

eff

(K-bus/field voltage)

Digital outputs

Control of polymer pump: feed flow rate and fault messages

Number of outputs

One-channel: 4 (KL2134)
Two-channel: 8 (KL2408)

Nominal load voltage

24 V DC (–15 % / +20 %)

Load type

ohmic, inductive lamp load

Max. output current

0.5 A (short-circuit proof) per channel

Reverse polarity protection

Yes

Electrical isolation

500 V

eff

(K-bus/field voltage)

Equipment properties

Dimensions (W x× H x× D)

One-channel: 191 Ч 120 Ч 96 mm (7.52 Ч 4.72 Ч 3.78 in)
Two-channel: 227 Ч 120 Ч 96 mm (8.94 Ч 4.72 Ч 3.78 in)

Mass

Approximately 0.9 kg (approximately 1.98 lb)

Environmental conditions

Working temperature

0 to 50 °C (32 to 122 °F)

Storage temperature

–25 to +85 °C (–13 to 185 °F)

Relative humidity

95 %, non-condensing

Miscellaneous

Pollution Degree

Protection Class

Installation Category

Maximum Altitude

2

1

II

2000 m (6.562 ft.)

Protection class

IP20

Installation

DIN rail EN 50022 35 × 15.0

1