Parameterization and operation

INPUT/OUTPUT LIMITS

CHANNEL 1

FEED FLOW LOW

Feed flow rate input signals below this value [m

3

/h] are set to

this value (to avoid low flow peaks).

m

3

/h

FEED FLOW HIGH

Feed flow rate input signals above this value [m

3

/h] are set to

this value (to avoid high flow peaks).

m

3

/h

FEED FLOW SMOOTHING

Feed flow measurement values are smoothed in line with this

parameter.

min

LIMIT TSS IN LOW

TSS measurement values from the influent that are below this

value [g/L] are set to this value (to avoid low peaks).

g/L

LIMIT MAX TSS IN HIGH

TSS measurement values from the influent that are above this

value [g/L] are set to this value (to avoid high peaks).

g/L

TSS IN SMOOTHING

The TSS measurement values from the influent are smoothed in

line with this parameter.

min

LIMIT TSS OUT LOW

The TSS values of the thickened sludge that are below this

value [g/L] are set to this value (to avoid low peaks).

g/L

LIMIT TSS OUT HIGH

The TSS values of the thickened sludge that are above this

value [g/L] are set to this value (to avoid high peaks).

g/L

TSS OUT SMOOTHING

The TSS measurement values from the effluent are smoothed in

line with this parameter.

min

POLYMER DOSING

MINIMUM

When FEED FLOW CONTROL is activated, measurement

values for the polymer dosing rate that are below this value

[m³/h] are set to this value (to avoid low peaks in the dosing

flow).

L/h

POLYMER DOSING

MAXIMUM

Any RTC calculation above this value [g/L] is set to this value

and delivered to the polymer pump.
When FEED FLOW CONTROL is activated, measurement

values for the polymer dosing rate that are above this value

[m³/h] are set to this value (to avoid high peaks in the dosing

flow).

L/h

CHANNEL 2

As per channel one

INPUTS

CHANNEL 1

MIN FEED FLOW

Minimum flow rate [m³/h] from the influent in accordance with

the 0/4 mA measurement signal.

m³/h

MAX FEED FLOW

Maximum flow rate [m³/h] from the influent in accordance with

the 20 mA measurement signal.

m³/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set in connected

flow measuring instrument).

MIN POLYMER FLOW

Minimum polymer dosing in [L/h] in accordance with the 0/4 mA

measurement signal.

L/h

MAX POLYMER FLOW

Maximum polymer dosing in [L/h] in accordance with the 20 mA

measurement signal.

L/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set on

connected flow measuring instrument).

CHANNEL 2

As per channel one

4.4.1

RTC113 ST-Module open and closed-loop controller (Continued)