Installation – Hach-Lange RTC113 ST-Module User Manual
Page 19

19
Installation
8x digital
output
1
KL2408
1
+24 V/0 V
1
Polymer pump on/off (24 V/0 V)
5
+24 V/0 V
1
Closed-loop control of the feed flow rate
active/inactive (24 V/0 V)
2
+24 V/0 V
1
Input signals OK (24 V), input signal faulty (0 V)
6
+24 V/0 V
1
RTC operational (24 V), RTC faulty (0 V)
3
+24 V/0 V
2
Polymer pump on/off (24 V/0 V)
7
+24 V/0 V
2
Closed-loop control of the feed flow rate
active/inactive (24 V/0 V)
4
+24 V/0 V
2
Input signals OK (24 V), input signal faulty (0 V)
8
+24 V/0 V
2
RTC operational (24 V), RTC faulty (0 V)
2x analog
output
KL4012
1(+) - 3(-)
0/4 to 20 mA
1
Output of the polymer pump flow rate
5(+) - 7(-)
0/4 to 20 mA
1
Output of the feed flow rate
2x analog
output
KL4012
1(+) - 3(-)
0/4 to 20 mA
2
Output of the polymer pump flow rate
5(+) - 7(-)
0/4 to 20 mA
2
Output of the feed flow rate
1x analog input KL3011
1(+) - 2(-)
0/4 to 20 mA
1
Input of the feed flow rate
1x analog input KL3011
1(+) - 2(-)
0/4 to 20 mA
1
Input of the polymer flow rate
1x analog input KL3011
1(+) - 2(-)
0/4 to 20 mA
2
Input of the feed flow rate
1x analog input KL3011
1(+) - 2(-)
0/4 to 20 mA
2
Input of the polymer flow rate
Bus termination KL9010
Bus termination
1
Ground to connection 3 and 7 or to the supply voltage connections
Table 4 Connections for the 2-channel RTC113 ST-Module
Module
Name
Connection Signal
Channel Function