Parameterization and operation

PRESELECT PROG.

CHANNEL 1

POLYMER DOSING

CONTROL

Based on the feed flow rate [m³/h] and measured TSS

concentration [g/L] from the influent, the polymer dosing rate

[L/h] is calculated such that it corresponds to the target specific

polymer dosing rate [g/kg].

Activation/

deactivation

FEED FLOW CONTROL

Based on the measured TSS concentration [g/L] and a fixed

polymer dosing rate [L/h], the feed flow [m

3

/h] is calculated such

that it corresponds to the specific polymer dosing rate [g/kg].

Activation/

deactivation

CLOSED LOOP EFFLUENT

CONTROL

If activated, the specific polymer dosing rate FACTOR

POLYMER DOSING is adjusted based on the difference

between the target and actual TSS concentration in the

thickened sludge.
The change in the specific dosing rate affects the polymer

dosing rate [L/h] in the POLYMER DOSING CONTROL module

and affects the feed flow rate in the FEED FLOW CONTROL

module.

Activation/

deactivation

CHANNEL 2

As per channel one

4.4.1

RTC113 ST-Module open and closed-loop controller (Continued)

RTC MODULES / PROGNOSYS