Parameterization and operation

4.6 PRESELECT PROG

4.6.1

POLYMER DOSING CONTROL

Based on the measured feed flow rate [m³/h] and the measured

TSS concentration [g/L] from the influent, the polymer dosing rate

[L/h] is calculated such that the setpoint corresponds to the

specific polymer dosing rate [g/kg].
Note: This open-loop control mode can only be activated if FEED FLOW

CONTROL is deactivated.

Note: The polymer flow rate is controlled via the RTC.

4.6.2

FEED FLOW CONTROL

Based on the measured TSS concentration [g/L] and the

specified polymer dosing rate [L/h], the feed flow rate is

calculated such that it corresponds with the specific polymer

dosing rate [g/kg] (FACTOR POLYMER DOSING).
Note: This open-loop control mode can only be activated if POLYMER

DOSING CONTROL is deactivated.

Note: The feed flow rate is controlled via the RTC.

4.6.3

CLOSED LOOP EFFLUENT CONTROL

If activated, the specific polymer dosing rate FACTOR POLYMER

DOSING is adjusted based on the difference between the target

and actual TSS concentration in the thickened sludge.
If FEED FLOW CONTROL is activated, the TSS load fed with the

sludge thickening is adjusted based on the difference between

the target and actual TSS concentration in the filtrate.
Note: This closed-loop control can only be activated if POLYMER

DOSING CONTROL (

section 4.6.1

) or FEED FLOW CONTROL

(

section 4.6.2

) is activated.

4.7 CONTROL PARAMETER

4.7.1

FACTOR POLYMER DOSING

Required specific polymer dosing [g/kg]. This parameter

determines how many grams of polymer per kilogram of TSS are

fed by the machine.

4.7.2

POLYMER CONCENTRATION

Polymer concentration [g/L] fed via the polymer pump.