Parameterization and operation

4.9.4

MIN POLYMER FLOW

Minimum polymer dosing in [L/h] in accordance with the 0/4 mA

measurement signal.

4.9.5

MAX POLYMER FLOW

Maximum polymer dosing in [L/h] in accordance with the 20 mA

measurement signal.

4.9.6

0/4...20 mA

Transfer range of the 0/4 to 20 mA current loop (as set in

connected flow measuring instrument).

4.10 OUTPUTS

4.10.1 MIN FEED FLOW

Minimum feed flow rate [m³/h] in accordance with 0/4 mA.

4.10.2 MAX FEED FLOW

Maximum feed flow rate [m³/h] in accordance with 20 mA.

4.10.3 0/4...20 mA

Transfer range of 0/4 to 20 mA current loop (as set in connected

flow measuring instrument).

4.10.4 MIN POLYMER FLOW

Minimum polymer pump delivery rate in accordance with 0/4 mA.

4.10.5 MAX POLYMER FLOW

Maximum polymer pump delivery rate in accordance with 20 mA.

4.10.6 0/4...20 mA

Transfer range of 0/4 to 20 mA current loop (as set in connected

flow measuring instrument).

4.10.7 CONTROL CYCLE

Pulse/pause mode for the polymer pump open-loop control for

dosing rates beneath the minimum polymer flow rate (MIN

POLYMER FLOW). The on/off duration in pulse/pause mode can

be affected by the duration of the CONTROL CYCLE. For

example, with a CONTROL CYCLE of 100 seconds and a dosing

control value of 60 %, the polymer pump is switched on for

60 seconds and switched off for 40 seconds. Short cycle times

increase the switching frequency but enable more precise

adaptation to individual requirements.
Note: CONTROL CYCLE must be divisible by MIN RUNTIME and

produce a whole number.