29

Parameterization and operation

4.7.3

MANUAL POLYMER DOSING

The RTC outputs the polymer dosing rate [L/h] if

FEED FLOW CONTROL is activated

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

The TSS measurement from the influent reports an error, or

The flow measurement from the influent reports an error.

4.7.4

MANUAL FEED FLOW

The RTC outputs the feed flow rate [m

3

/h] if

POLYMER DOSING CONTROL is activated

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

The TSS measurement at the inlet reports an error, or

The flow measurement from the influent reports an error.

4.7.5

MAX DECREASE CLOSED L

This value defines the maximum decrease of the specific polymer

dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED

LOOP EFFLUENT CONTROL is selected.

4.7.6

MAX INCREASE CLOSED L

This value defines the maximum increase of the specific polymer

dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED

LOOP EFFLUENT CONTROL is selected.

4.7.7

SET-POINT TSS

Required setpoint of the TSS concentration in the thickened

sludge.
Note: · This parameter is only considered if CLOSED LOOP EFFLUENT

CONTROL (

section 4.6.3

) is activated.

4.7.8

P GAIN TSS

Proportional gain for the PID closed-loop controller for the TSS

concentration in the thickened sludge.
Note: P GAIN TSS [L/g] is divided by 100 before it is multiplied by the

deviation of the actual TSS concentration from the required TSS

setpoint.

4.7.9

INTEGRAL TIME TSS

Integral time for the PID closed-loop controller for the TSS

concentration in the thickened sludge.
Note: INTEGRAL TIME TSS is set to "0" to deactivate the integral part of

the PI open-loop controller.