Parameterization and operation

4.7.3

MANUAL POLYMER DOSING

The RTC outputs the polymer dosing rate [L/h] if
•

FEED FLOW CONTROL is activated

•

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

•

The TSS measurement from the influent reports an error, or

•

The flow measurement from the influent reports an error.

4.7.4

MANUAL FEED FLOW

The RTC outputs the feed flow rate [m

3

/h] if

•

POLYMER DOSING CONTROL is activated

•

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

•

The TSS measurement at the inlet reports an error, or

•

The flow measurement from the influent reports an error.

4.7.5

MAX DECREASE CLOSED L

This value defines the maximum decrease of the specific polymer

dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED

LOOP EFFLUENT CONTROL is selected.

4.7.6

MAX INCREASE CLOSED L

This value defines the maximum increase of the specific polymer

dosing rate FACTOR POLYMER DOSING [g/kg] if CLOSED

LOOP EFFLUENT CONTROL is selected.

4.7.7

SET-POINT TSS

Required setpoint of the TSS concentration in the thickened

sludge.
Note: · This parameter is only considered if CLOSED LOOP EFFLUENT

CONTROL (

section 4.6.3

) is activated.

4.7.8

P GAIN TSS

Proportional gain for the PID closed-loop controller for the TSS

concentration in the thickened sludge.
Note: P GAIN TSS [L/g] is divided by 100 before it is multiplied by the

deviation of the actual TSS concentration from the required TSS

setpoint.

4.7.9

INTEGRAL TIME TSS

Integral time for the PID closed-loop controller for the TSS

concentration in the thickened sludge.
Note: INTEGRAL TIME TSS is set to "0" to deactivate the integral part of

the PI open-loop controller.