Installation

3.4 Connection to the automation unit on the plant side

The one-channel and two-channel versions of the ST-Module are equipped with various

modules that must be connected to the plant automation system.

The feed flow rate must be provided to the ST-Module as a 0/4 to 20 mA signal.

The polymer flow rate must be provided (on both versions) to the ST-Module as a

0/4 to 20 mA signal.

The status signal of the thickened sludge pump (on/off) must be a digital input signal

(24 V/0 V).

The polymer pump can be operated in pulse/pause mode (PWM).

The status signals and fault indications are output as 0 V/24 V signals.

Measurement errors are shown 5 minutes after the error occurs. In the event of a new

startup (return of power supply), the unit is set back to ON (24 V) after approximately

1 minute and 40 seconds if there are no measurement errors.

In the event of a new startup (return of power supply), the RTC operating signal is set

back to ON (24 V) after approximately 1 minute and 25 seconds.

Table 3 Connections for the 1-channel RTC113 ST-Module

Module

Name

Connection Signal

Function

2x digital input

KL1002

1

Input + 24 V/0 V

Status of thickened sludge pump (on/off)

2

Source + 24 V

24 V for relay

4x digital output

1

KL2134

1

+24 V/0 V

Polymer pump on/off (24 V/0 V)

5

+24 V/0 V

Closed-loop control of the feed flow rate

active/inactive (24 V/0 V)

4

+24 V/0 V

Input signals OK (24 V), input signal faulty (0 V)

8

+24 V/0 V

RTC operational (24 V), RTC faulty (0 V)

2x analog output

KL4012

1(+) - 3(-)

0/4 to 20 mA

Output of the polymer pump flow rate

5(+) - 7(-)

0/4 to 20 mA

Output of the feed flow rate

1x analog input

KL3011

1(+) - 2(-)

0/4 to 20 mA

Input of the feed flow rate

1x analog input

KL3011

1(+) - 2(-)

0/4 to 20 mA

Input of the polymer flow rate

Bus termination

KL9010

Bus termination

1

Ground to connection 3 and 7 or to the supply voltage connections

Table 4 Connections for the 2-channel RTC113 ST-Module

Module

Name

Connection Signal

Channel Function

4x digital input

KL1002

1

Input + 24 V/0 V

1

Status of thickened sludge pump (on/off)

2

Source + 24 V

1

24 V for relay

5

Input + 24 V/0 V

2

Status of thickened sludge pump (on/off)

6

Source + 24 V

2

24 V for relay