Parameterization and operation
OUTPUTS
CHANNEL 1
MIN FEED FLOW
Minimum feed flow rate [m³/h] in accordance with 0/4 mA.
m³/h
MAX FEED FLOW
Maximum feed flow rate [m³/h] in accordance with 20 mA.
m³/h
0/4...20mA
Transfer range of 0/4 to 20 mA current loop (as set on
connected flow measuring instrument).
MIN POLYMER FLOW
Minimum polymer pump delivery rate in accordance with
0/4 mA.
L/h
MAX POLYMER FLOW
Maximum polymer pump delivery rate in accordance with
20 mA.
L/h
0/4...20mA
Transfer range of 0/4 to 20 mA current loop (as set on
connected flow measuring instrument).
CONTROL CYCLE
Pulse/pause mode for the polymer pump open-loop control for
dosing rates beneath the minimum polymer flow rate (MIN
POLYMER FLOW). The on/off duration in pulse/pause mode
can be affected by the duration of the CONTROL CYCLE. For
example, with a CONTROL CYCLE of 100 seconds and a
dosing control value of 60 %, the polymer pump is regularly
switched on for 60 seconds and switched off for 40 seconds.
Short cycle times increase the switching frequency but enable
more precise adaptation to individual requirements. CONTROL
CYCLE should be divisible by MIN RUNTIME and produce a
whole number.
s
MIN RUNTIME
The minimum ON time in pulse/pause dosing mode. The pump
is not activated for periods shorter than this. The MIN RUNTIME
must be shorter than the duration of the CONTROL CYCLE.
s
CHANNEL 2
As per channel one
MODBUS
ADDRESS
Start address of an RTC within the Modbus network. Default
setting: 41–61
DATA ORDER
Specifies the register order within a double word. Presetting:
NORMAL
DATALOG INTRVL
Indicates the interval in which the data is saved in the log file.
[min]
SET DEFAULTS
Restores the factory settings.
MAINTENANCE
RTC DATA
RTC MEASUREMEN
Specifies the value measured by the RTC, e. g. the influent
measurement.
RTC ACTUAT VAR
Specifies the variable calculated by the RTC, e. g. whether the
aeration should be switched on or off.
DIAG/TEST
EEPROM
Hardware test
RTC COMM TO
Communication time-out
RTC CRC
Communication check sum
MODBUS ADDRESS
Here, the address is displayed where the communication
actually takes place. Presetting: 41
4.4.1
RTC113 ST-Module open and closed-loop controller (Continued)
RTC MODULES / PROGNOSYS
RTC MODULES
RTC