Parameterization and operation

4.8.7

LIMIT TSS OUT LOW

TSS measurement values for the thickened sludge that are below

this value [g/L] are set to this value (to avoid low peaks).

4.8.8

LIMIT TSS OUT HIGH

TSS measurement values for the thickened sludge that are

above this value [m

3

/h] are set to this value (to avoid high peaks).

4.8.9

TSS OUT SMOOTHING

TSS measurement values from the effluent are smoothed in line

with this parameter.

SMOOTHING = 1: The signal is not smoothed.
SMOOTHING = 2: Smoothing is performed over 3 minutes.
SMOOTHING = 3: Smoothing is performed over 5 minutes.
SMOOTHING = 5: Smoothing is performed over 12 minutes.
SMOOTHING = 10: Smoothing is performed over

25 minutes.

4.8.10 POLYMER DOSING MINIMUM

RTC calculations below this value [g/L] are set to this value and

transferred to the polymer pump.
Note: When FEED FLOW CONTROL is activated, measurement values

for the polymer dosing rate that are below this value [m

3

/h] are set to this

value (to avoid low peaks in the dosing flow).

4.8.11 POLYMER DOSING MAXIMUM

RTC calculations above this value [g/L] are set to this value and

transferred to the polymer pump.
Note: When FEED FLOW CONTROL is activated, measurement values

for the polymer dosing rate that are above this value [m

3

/h] are set to this

value (to avoid high peaks in the dosing flow).

4.9 INPUTS

4.9.1

MIN FEED FLOW

Minimum flow rate [m³/h] from the influent in accordance with the

0/4 mA measurement signal.

4.9.2

MAX FEED FLOW

Maximum flow rate [m³/h] from the influent in accordance with the

20 mA measurement signal.

4.9.3

0/4...20 mA

Transfer range of the 0/4 to 20 mA current loop (as set in

connected flow measuring instrument).