6

MODEL

FOR MOTORS

INPUT (50-60 Hz)

OUTPUT

HEAT LOSS

NUMBER

RATED

INPUT

CURRENT

POWER

CURRENT

(WATTS)

HP

kW

PHASE

(AMPS) (NOTE 1)

(kVA)

(AMPS)

(NOTE 2)

120/208/240 VAC

0 - 230/200/230 VAC

174492

1

0.75

1

16.6/9.6/8.3

2.0

4.2/4.8/4.2

48

174445

1.5

1.1

1

24/13.9/12.0

2.9

6.0/6.9/6.0

73

208/240 Vac

0 - 200/230 Vac

174452

0.25

0.20

1

3.6/3.2

0.76

1.6/1.4

19

174452

0.25

0.20

3

1.9/1.7

0.71

1.6/1.4

19

174453

0.5

0.37

1

5.4/4.7

1.2

2.5/2.2

26

174453

0.5

0.37

3

3.1/2.7

1.1

2.5/2.2

26

174454

1

0.75

1

10.6/9.2

2.2

4.8/4.2

49

174454

1

.075

3

5.8/5.1

2.1

4.8/4.2

49

174493

1.5

1.1

1

13.9/12.0

2.9

6.9/6.0

82

174493

1.5

1.1

3

8.0/6.9

2.9

6.9/6.0

82

174494

2

1.5

1

14.8/12.9

3.1

7.8/6.8

86

174494

2

1.5

3

9.1/7.9

3.2

7.8/6.8

86

174495

3

2.2

1

19.7/17.1

4.1

11.0/9.6

130

174495

3

2.2

3

12.4/10.8

4.4

11.0/9.6

130

174444

5

3.7

1

29/26

6.1

17.5/15.2

212

174444

5

3.7

3

19.6/17.1

7.1

17.5/15.2

212

208/240 Vac

0 - 200/230 Vac

174455

1

0.75

3

5.8/5.1

2.1

4.8/4.2

41

174456

1.5

1.1

3

8.0/6.9

2.9

6.9/6.0

69

174457

2

1.5

3

9.1/7.9

3.3

7.8/6.8

78

174458

3

2.2

3

12.4/10.8

4.5

11.0/9.6

117

174446

5

3.7

3

19.6/17.1

7.1

17.5/15.2

187

174438

7.5

5.5

3

28/25

10.3

25/22

286

174439

10

7.5

3

34/32

13.1

30/28

379

174429

15

11

3

54/48

20.0

48/42

476

174430

20

15

3

65/61

25.4

58/54

648