DESCRIPTION OF PI PARAMETERS

P10

TB-13A FUNCTION SELECT

12

KEYPAD SETPOINT: This option has been added so that the

▲ and ▼ buttons on the front

of the drive can be used as the PI setpoint reference source. Closing TB-13A to TB-2 will enable
the PI mode and the

▲ and ▼ buttons can be used to select the desired process setpoint.

P11

TB-13B FUNCTION SELECT

09

KEYPAD SETPOINT: This option has been added so that the

▲ and ▼ buttons on the front

of the drive can be used as the PI setpoint reference source. Closing TB-13B to TB-2 will enable
the PI mode and the

▲ and ▼ buttons can be used to select the desired process setpoint.

P12

TB-13C FUNCTION SELECT

10

KEYPAD SETPOINT: This option has been added so that the

▲ and ▼ buttons on the front

of the drive can be used as the PI setpoint reference source. Closing TB-13C to TB-2 will enable
the PI mode and the

▲ and ▼ buttons can be used to select the desired process setpoint.

P61

PI MODE

This parameter must be set to match the type of system and the type of feedback signal used. A direct
acting system is one that requires the motor speed to increase as the feedback signal decreases, while a
reverse acting system requires the motor speed to decrease as the feedback signal decreases.

01

DISABLED

Disables the PI function to allow standard drive operation.

02

NORMAL 4-20 mA

Enables the PI function for a direct acting system with a 4-20 mA
feedback signal.

03

NORMAL 0-10 VDC

Enables the PI function for a direct acting system with a 0-10 VDC
feedback signal.

04

REVERSE 4-20 mA

Enables the PI function for a reverse acting system with a 4-20 mA
feedback signal.

05

REVERSE 0-10 VDC

Enables the PI function for a reverse acting system with a 0-10 VDC
feedback signal.

When PI is disabled, the drive will operate in an OPEN LOOP mode, responding directly to a speed
reference source selected using STANDARD SPEED SOURCE (Parameter 05) or terminals TB-13A,
13B, and/or 13C).

P62

MIN FEEDBACK

This parameter should be set to the value of the process variable that corresponds to the minimum
transducer feedback signal (0 VDC or 4 mA). See the example below: