LEESON SM-Plus Series Sub-Micro Inverters User Manual

Page 41

Advertising
background image

06

EXTERNAL FAULT: Sets TB-13C as a normally closed external fault input. If TB-13C is open
with respect to TB-2, the drive will fault.

07

REMOTE KEYPAD: Selects the optional remote keypad as the control source. Refer to
Parameter 14 - CONTROL.

08

DB FAULT: Sets TB-13C as a dynamic braking fault input when using the optional dynamic
braking module. When this input is activated by the dynamic braking module, the drive will trip
into a “dF” fault and the motor will coast to a stop. Refer to the manual included with the
Dynamic Braking option.

09

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into Parameter
42 - ACCEL/DECEL #2.

P13

TB-15 OPEN COLLECTOR OUTPUT

This selects the status indication for the open-collector output at TB-15, and has the same
selections as Parameter 6 - TB-14 OPEN COLLECTOR OUTPUT.

P14

CONTROL

This selects the source of START/STOP and direction commands.

01

TERMINAL STRIP ONLY: The drive will only respond to START/STOP and direction
commands from the terminal strip.

02

REMOTE KEYPAD ONLY: The drive will only respond to START/STOP and direction
commands from the optional remote keypad.

03

TERMINAL STRIP OR REMOTE KEYPAD: Terminal TB-13A or TB-13C can be used to
select terminal strip control or remote keypad control. See Parameters 10 and 12.

NOTE: This STOP button on the optional remote keypad is always active as long as the serial link
remains intact.

P15

SERIAL LINK

This parameter configures the drive for serial communications. The options are listed by baud rate,
number of data bits, parity, number of stop bits, and whether the watchdog timer is enabled or disabled.

The watchdog timer will stop the drive after 10 seconds of no serial activity to safeguard against a failed
serial link. During set-up or troubleshooting, it may be useful to disable the watchdog timer, but it is not
recommended to run normally without the watchdog timer.

Controlling the drive from the serial link without the watchdog timer could cause

damage to equipment and/or injury to personnel!