LEESON SM-Plus Series Sub-Micro Inverters User Manual

Page 39

Advertising
background image

P10

TB-13A FUNCTION SELECT

This selects the function of terminal TB-13A. Closing TB-13A to TB-2 (or opening in the case of
settings 7 and 10) activates the selected function. The following functions can be selected:

01

NONE: Disables the TB-13A function.

02

0-10 VDC: Selects a 0-10 VDC signal (at TB-5) as the AUTO speed reference input.

03

4-20 mA: Selects a 4-20 mA signal (at TB-25) as the AUTO speed reference input.

04

PRESET SPEED #1: Selects PRESET SPEED #1 as the AUTO speed reference. The drive will
operate at the frequency programmed into Parameter 31.

05

RUN REVERSE: Close TB-13A to TB-2 to RUN in the reverse direction, and open to STOP.
This setting forces TB-12 to act as RUN FWD, requiring a maintained contact to RUN in the
forward direction. TB-1 must be closed to TB-2 for this function to operate.

06

START REVERSE: Momentarily close TB-13A to TB-2 to START the drive in the reverse
direction. Momentarily open TB-1 to TB-2 to STOP. This setting forces TB-12 to act as START
FWD, requiring a momentary contact to START in the forward direction.

07

EXTERNAL FAULT: Sets TB-13A as a normally closed external fault input. If TB-13A is open
with respect to TB-2, the drive will fault.

08

REMOTE KEYPAD: Selects the optional remote keypad as the control source. Refer to
Parameter 14 - CONTROL.

09

DB FAULT: Sets TB-13A as a dynamic braking fault input when using the optional dynamic
braking module. When this input is activated by the dynamic braking module, the drive will trip
into a “dF” fault and the motor will coast to a stop. Refer to the manual included with the
Dynamic Braking option.

10

AUXILIARY STOP: When TB-13A is opened with respect to TB-2, the drive will decelerate to
a STOP (even if STOP METHOD is set to COAST) at the rate set into Parameter 42 -
ACCEL/DECEL #2.

11

ACCEL/DECEL #2: Selects the acceleration and deceleration time programmed into Parameter
42 - ACCEL/DECEL #2.

NOTE: In order for the RUN REVERSE and START REVERSE function to operate, Parameter 17 -
ROTATION DIRECTION must be set to FORWARD AND REVERSE (02).

P11

TB-13B FUNCTION SELECT

This selects the function of terminal TB-13B. Closing TB-13B to TB-2 (or opening in the case of
setting 08) activates the selected function. The following functions can be selected:

35