21

11.5

SPEED POT AND PRESET SPEED CONTROL

Shown below is the wiring for SPEED POT and/or PRESET SPEED control, and either a two-wire or
three-wire start/stop circuit:

NOTES:

1.

Program the PRESET SPEEDS (Parameters 31-37) to the desired values.

2.

Program TB-13A (Parameter 10) to PRESET SPEED #1 (04). TB-13B (parameter 11) to
PRESET SPEED #2 (04), and TB-13C (Parameter 12) to PRESET SPEED #3 (04). To select a
preset speed, close the appropriate TB-13 terminal(s) to TB-2 (refer to Parameters 31-37 for the
Preset Speed Activation table).

3.

If reverse rotation is also required, TB-13A cannot be used as a PRESET SPEED SELECT.
TB-13A must be programmed to select RUN REVERSE (05) or START REVERSE (06), leaving
only TB-13B and TB-13C to select preset speeds.

4.

For speed pot control, program Parameter 05 - STANDARD SPEED SOURCE for 0-10 VDC
(03). If none of the preset speeds are selected (all of the TB-13 terminals are open), the drive will
respond to the speed pot.

ST

OP

1 2

The TB-2 terminals are internally connected to each other

5

11 12 2 14 13A 13B 13C 15 25

2 30 31 TXA TXB

6

COMMON

0-10

VDC

INPUT

ST

AR

T

10

VDC

SUPPL

Y

COMMON

PRESET

SPEED

SELECT

PRESET

SPEED

SELECT

PRESET

SPEED

SELECT

2.5K-10K½