DC BUS VOLTAGE

This displays the DC bus voltage in percent of nominal. Nominal DC bus voltage is determined by
multiplying the drive’s nameplate input voltage rating by 1.4.

P53

MOTOR VOLTAGE

This displays the output voltage in percent of the drive’s nameplate output voltage rating.

P54

MOTOR LOAD

This displays the motor load in percent of the drive’s output current rating.

P55

0-10 VDC ANALOG INPUT

This displays the level of the 0-10 VDC analog input signal at TB-5. A reading of 100%
indicates a 10 VDC input at TB-5.

P56

4-20 mA ANALOG INPUT

This displays the level of the 4-20 mA analog input signal at TB-25. A reading of 20% indicates a 4 mA
input at TB-25, and a reading of 100% indicates a 20 mA input at TB-25.

P57

TERMINAL STRIP STATUS

This indicates that status of several terminals using the vertical segments of the LED display. An
illuminated segment indicates that the particular terminal is closed with respect to TB-2. The CHARGE
RELAY is not a terminal, and should always be illuminated. See the diagram below:

45

TB-1

TB-12

TB-13A

TB-13B

TB-13C

TB-14

TB-15

CHARGE

RELAY