43

Example: A 0-10 VDC signal is required to indicate 0-150% load. Setting this parameter to 150% will
yield 10 VDC at 150% load.

P42

ACCEL / DECEL #2

This parameter sets the second acceleration and deceleration rate of the drive. To activate this acceleration
and deceleration rate, use terminal TB-13A, TB-13B or TB-13C. TB-13A and TB-13B can be set to
AUXILIARY STOP which will cause the drive to decelerate to a stop according to the time programmed
in this parameter. TB-13C can be set to ACCEL/DECEL #2, which causes the drive to accelerate and
decelerate according to the time programmed in this parameter.

P43

SERIAL ADDRESS

If a serial link is being used to communicate with multiple drives, each drive must be given a different
address (from 1 to 247) so that an individual drive in the network can be accessed.

P44

PASSWORD

This allows the PASSWORD to be changed to any number between 000 and 999. Setting
PASSWORD to 000 disables the password function.

NOTE: The factory default password is 225.

P47

CLEAR FAULT HISTORY

01

MAINTAIN: Maintains the FAULT HISTORY (Parameter 50) entries for troubleshooting.

02

CLEAR: Erases the FAULT HISTORY (Parameter 50) entries.

P48

PROGRAM SELECTION

This is used to select whether the drive will operate according to the user settings or the optional OEM
default settings, and to reset the parameters to default settings. Refer to Section 13.2.

01

OPERATE WITH USER SETTINGS: The drive will operate according to the users settings.
Operation in USER mode allows the parameter values to be changed to suit any application.

02

OPERATE WITH OEM DEFAULTS: The drive will operate according to the optional OEM
default settings, which configure the drive for a specific application. When operating in OEM
mode, the parameter values can be viewed, but not changed. If an attempt is made to change a
parameter setting, the display will flash “GE”. If the drive is not programmed with OEM default
settings, the display will flash “GF” if this option is selected.

03

RESET OEM: Resets the user parameters to the OEM default settings. If the drive is not
programmed with OEM default settings, the display will flash “GF” if this option is selected.