P29

ACCELERATION BOOST

ACCELERATION BOOST helps accelerate high-inertia loads. During acceleration, the output voltage
is increased to increase motor torque. Once the motor reaches the new speed setpoint, the boost is turned
off and the output voltage returns to the normal value.

P30

SLIP COMPENSATION

SLIP COMPENSATION is used to counteract changes in motor speed (slip) caused by changes in load.
In a standard AC induction motor, the shaft speed decreases as load increases, and increases as load
decreases. By increasing or decreasing the output frequency in response to an increasing or decreasing
load, the slip is counteracted and speed is maintained. Most standard NEMA B motors have a 3% slip
rating.

P31 - P37 PRESET SPEED #1 - #7

Preset speeds are activated by contact closures between TB-2 and TB-13A, 13B, and 13C. The TB-13
terminals must be programmed as preset speed selects using Parameters 10-12.

NOTE 1: Preset speeds can operate below the frequency defined by the minimum frequency parameter
(Parameter 23). The range of adjustment for the preset speeds is from 0 Hz to the maximum frequency
(Parameter 24).

Refer to the table below for activation of the preset speeds using the TB-13 terminals.

NOTE 2: When a TB-13 terminal is programmed for a function other than a preset speed select, it is
considered OPEN for the table above.

Preset Speed #6 and #7 can also be used as skip frequencies to restrict the drive from operating at
frequencies that cause vibration in the system. See Parameter 38 below.

P38

SKIP BANDWIDTH

The SM-Plus

drive has two skip frequencies that can be used to lock out critical frequencies that cause

mechanical resonance in the system. Once SKIP BANDWIDTH is set to a value other than 0.0 Hz, the
skip frequencies are enabled. When the skip frequency function is enabled, PRESET SPEED #6 and #7
are used as the skip frequencies. SKIP BANDWIDTH sets the range above the skip frequencies that the
drive will not operate within.

41

SPEED #

TB-13A

TB-13B

TB-13C

1

CLOSED

OPEN

OPEN

2

OPEN

CLOSED

OPEN

3

OPEN

OPEN

CLOSED

4

CLOSED

CLOSED

OPEN

5

CLOSED

OPEN

CLOSED

6

OPEN

CLOSED

CLOSED

7

CLOSED

CLOSED

CLOSED