LEESON SM-Plus Series Sub-Micro Inverters User Manual

Page 56

Advertising
background image

B.3

SETPOINT REFERENCES

The following references can be used to adjust the process setpoint:

1.

Keypad (

▲ and ▼ buttons)

2.

0-10 VDC signal (from speed pot or other source)

3.

4-20 mA signal

4.

Preset Setpoints (using Preset Speeds #4 and #5)

NOTE: The setpoint reference and the PI feedback cannot be the same signal. If the drive is mistakenly
programmed so that the setpoint reference is the same as the feedback reference, the setpoint reference
will default to the

▲ and ▼ buttons.

B.4

ADDITIONS TO THE STANDARD PARAMETER MENU

NO.

PARAMETER NAME

RANGE OF ADJUSTMENT

FACTORY
DEFAULT

MIN ALARM (11), MAX ALARM (12),

06

TB-14 OUTPUT

MIN/MAX ALARM (13), INV MIN ALARM (14),

HIGH (01)

13

TB-15 OUTPUT

INV MAX ALARM (15),

INV MIN/MAX ALARM (16)

10

TB-13A FUNCTION

KEYPAD SETPOINT (12)

NONE (01)

11

TB-13B FUNCTION

KEYPAD SETPOINT (09)

NONE (01)

12

TB-13C FUNCTION

KEYPAD SETPOINT (10)

NONE (01)

45

SPD AT MIN SIGNAL

MINIMUM FREQ - 999.0 Hz

0.0 Hz

46

SPD AT MAX SIGNAL

MINIMUM FREQ - 999.0 Hz

0.0 Hz

61

PI MODE

OFF (01), NORMAL 4-20 mA (02),

OFF (01)

NORMAL 0-10 VDC (03),

REVERSE 4-20 mA (04),

REVERSE 0-10 VDC (05)

62

MIN FEEDBACK

0.0 - 999.0

0.0

63

MAX FEEDBACK

0.0 - 999.0

100.0

64

PROPORTIONAL GAIN

0.0 - 999.0

5.0 %

65

INTEGRAL GAIN

0.0 - 999.9 SEC

0.0 SEC

66

PI ACCEL/DECEL

0.0 - 999.0 SEC

20.0 SEC

67

MIN ALARM

0.0 - 999.0

0.0

68

MAX ALARM

0.0 - 999.0

0.0

69

0-10 VDC FEEDBACK

(VIEW - ONLY)

(N/A)

70

4-20 mA FEEDBACK

(VIEW - ONLY)

(N/A)

71

ACTUAL FEEDBACK

(VIEW - ONLY)

(N/A)

74

ANALOG INPUT FILTER

1-1000

2

75

SLEEP DELAY

0.0 - 360 SEC

0.0 Hz

76

SLEEP DELAY

0.0 - 300 SEC

30.0 SEC

77

SLEEP BANDWIDTH

MIN FEEDBACK - MAX FEEDBACK

0.0

52