B.3
SETPOINT REFERENCES
The following references can be used to adjust the process setpoint:
1.
Keypad (
▲ and ▼ buttons)
2.
0-10 VDC signal (from speed pot or other source)
3.
4-20 mA signal
4.
Preset Setpoints (using Preset Speeds #4 and #5)
NOTE: The setpoint reference and the PI feedback cannot be the same signal. If the drive is mistakenly
programmed so that the setpoint reference is the same as the feedback reference, the setpoint reference
will default to the
▲ and ▼ buttons.
B.4
ADDITIONS TO THE STANDARD PARAMETER MENU
NO.
PARAMETER NAME
RANGE OF ADJUSTMENT
FACTORY
DEFAULT
MIN ALARM (11), MAX ALARM (12),
06
TB-14 OUTPUT
MIN/MAX ALARM (13), INV MIN ALARM (14),
HIGH (01)
13
TB-15 OUTPUT
INV MAX ALARM (15),
INV MIN/MAX ALARM (16)
10
TB-13A FUNCTION
KEYPAD SETPOINT (12)
NONE (01)
11
TB-13B FUNCTION
KEYPAD SETPOINT (09)
NONE (01)
12
TB-13C FUNCTION
KEYPAD SETPOINT (10)
NONE (01)
45
SPD AT MIN SIGNAL
MINIMUM FREQ - 999.0 Hz
0.0 Hz
46
SPD AT MAX SIGNAL
MINIMUM FREQ - 999.0 Hz
0.0 Hz
61
PI MODE
OFF (01), NORMAL 4-20 mA (02),
OFF (01)
NORMAL 0-10 VDC (03),
REVERSE 4-20 mA (04),
REVERSE 0-10 VDC (05)
62
MIN FEEDBACK
0.0 - 999.0
0.0
63
MAX FEEDBACK
0.0 - 999.0
100.0
64
PROPORTIONAL GAIN
0.0 - 999.0
5.0 %
65
INTEGRAL GAIN
0.0 - 999.9 SEC
0.0 SEC
66
PI ACCEL/DECEL
0.0 - 999.0 SEC
20.0 SEC
67
MIN ALARM
0.0 - 999.0
0.0
68
MAX ALARM
0.0 - 999.0
0.0
69
0-10 VDC FEEDBACK
(VIEW - ONLY)
(N/A)
70
4-20 mA FEEDBACK
(VIEW - ONLY)
(N/A)
71
ACTUAL FEEDBACK
(VIEW - ONLY)
(N/A)
74
ANALOG INPUT FILTER
1-1000
2
75
SLEEP DELAY
0.0 - 360 SEC
0.0 Hz
76
SLEEP DELAY
0.0 - 300 SEC
30.0 SEC
77
SLEEP BANDWIDTH
MIN FEEDBACK - MAX FEEDBACK
0.0