LEESON SM-Plus Series Sub-Micro Inverters User Manual

Page 15

Advertising
background image

7.2

INPUT FUSING AND DISCONNECT REQUIREMENTS

A circuit breaker or a disconnect switch with fuses must be provided in accordance with the National
Electric Code (NEC) and all local codes. Refer to the following table for proper fuse/circuit breaker
rating and wire size.

11

INPUT FUSE / CIRCUIT BREAKER RATINGS AND WIRE SIZE REQUIREMENTS (Note 1)

208/240 Vac, 1 phase

208/240 Vac, 3 phase

400/480 Vac, 3 phase

480/490 Vac, 3 phase

Catalog

Fuse Rating

Wire Size

Catalog

Fuse Rating

Wire Size

Catalog

Fuse Rating

Wire Size

Catalog

Fuse Rating

Wire Size

HP

Number

Note(2)

AWG (mm

2

)

Number

Note(2)

AWG (mm

2

)

Number

Note(2)

AWG (mm

2

)

Number

Note(2)

AWG (mm

2

)

0.25 174452

10A

14(1.5) 174452

10A

14(1.5)

0.5

174453

10A

14(1.5) 174453

10A

14(1.5)

174459

10A

14(1.5)

1

174454

15A

12(1.5)

174454

10A

14(1.5)

174460

10A

14(1.5)

174464

10A

14(1.5)

174455

1.5

174493

20A

12(2.5)

174493

12/10A

14(1.5)

174461

10A

14(1.5)

174456

2

174494

25/20A

10(2.5)

174494

15/12A

12(2.5)

174462

10A

14(1.5)

174491

10A

14(1.5)

174457

3

174495

30/25A

10(4.0)

174495

20/15A

10(4.0)

174463

10A

14(1.5)

174497

10A

14(1.5)

174458

5

174444

45/40A

10(6.0)

174444

30/25A

8(6.0)

174447

15A

14(1.5)

174448

12A

14(1.5)

174446

7.5

174438

45/40A

8(6.0)

174440

20A

12(2.5)

174442

20A

14(1.5)

10

174439

50/50A

8(10)

174441 30/25A

10(4.0)

174443

20A

12(2.5)

15

174429

80/75A

6(16)

174431 40/35A

8(6.0)

174434

30A

10(4.0)

20

174430 100/90A

4(25)

174432 50/45A

8(10)

174435

40A

8(6.0)

25

174433 70/60A

6(16)

174436

45A

8(6.0)

30

174500 80/70A

6(16)

NOTE 1: Applicable national and local electrical codes take precedence over recommendations in this table.
NOTE 2: Use UL Class CC or Class T fast-acting, current limiting type fuses. Select fuses with low I

2

T values, rated at

200,000 AIC. Recommended fuses are Bussman KTK-R, JJN, and JJS. Similar fuses with equivalent ratings by other
manufacturers may also be acceptable.