30

FACTORY

NO.

PARAMETER NAME

RANGE OF ADJUSTMENT

DEFAULT

(NOTE 1)

27

BASE FREQUENCY

25.0 - 500.0 Hz (NOTE 4)

60.0 Hz

28

FIXED BOOST

0.0 - 30.0 %

1.0 %

29

ACCEL BOOST

0.0 - 20.0 %

0.0 %

30

SLIP COMPENSATION

0.0 - 5.0 %

0.0 %

31-37

PRESET SPEEDS

0.0 - MAXIMUM FREQUENCY

0.0 Hz

38

SKIP BANDWIDTH

0.0 - 10.0 Hz

0.0 Hz

39

SPEED SCALING

0.0 - 6500.0

0.0

40

FREQUENCY SCALING

3.0 -2 000.0 Hz

60.0 Hz

41

LOAD SCALING

10 - 200 %

200 %

42

ACCEL / DECEL #2

0.1 - 3600.0 SEC

20.0 SEC

43

SERIAL ADDRESS

1 - 247

1

44

PASSWORD

000 - 999

225

47

CLEAR HISTORY

MAINTAIN (01), CLEAR (02)

MAINTAIN (01)

48

PROGRAM

USER SETTINGS (01), OEM SETTINGS (02),

USER

SELECTION

RESET OEM (03), RESET 60 (04),

SETTINGS (01)

RESET 50 (05), TRANSLATE (06)

50

FAULT HISTORY

(VIEW - ONLY)

(N/A)

51

SOFTWARE CODE

(VIEW - ONLY)

(N/A)

52

DC BUS VOLTAGE

(VIEW - ONLY)

(N/A)

53

MOTOR VOLTAGE

(VIEW - ONLY)

(N/A)

54

LOAD

(VIEW - ONLY)

(N/A)

55

0 - 10 VDC INPUT

(VIEW - ONLY)

(N/A)

56

4-20 mA INPUT

(VIEW - ONLY)

(N/A)

57

TB STRIP STATUS

(VIEW - ONLY)

(N/A)

58

KEYPAD STATUS

(VIEW - ONLY)

(N/A)

59

TB-30 OUTPUT

(VIEW - ONLY)

(N/A)

60

TB-31 OUTPUT

(VIEW - ONLY)

(N/A)

NOTE 1: Factory defaults are shown for a 60 Hz base frequency. See Parameter 48 for 50 Hz base
frequency.
NOTE 4: Maximum setting is 1300.0 Hz (factory default is 999.9) on drives with High Output
Frequency option. Consult the factory.

PARAMETER MENU (cont)