Fault time data record – TREND NX Variable Speed Drives User Manual

Page 100

Advertising
background image

CONTROL KEYPAD

vacon • 83

24-hour support +358 (0)40 837 1150 • Email: [email protected]

7

7.3.4.3 Fault

time data record

When a fault occurs the information described above in 7.3.4 is displayed. By pushing the

Menu button

right

here you will enter the

Fault time data record menu

indicated by T.1

T.13. In this menu, some

selected important data valid at the time of the fault are recorded. This feature is intended to help the user
or the service person to determine the cause of fault.

The data available are:

T.1

Counted operation days

(Fault 43: Additional code)

d

T.2

Counted operation hours

(Fault 43: Counted operation days)

hh:mm:ss

(d)

T.3

Output frequency

(Fault 43: Counted operation hours)

Hz

(hh:mm:ss)

T.4

Motor current

A

T.5

Motor voltage

V

T.6

Motor power

%

T.7

Motor torque

%

T.8

DC voltage

V

T.9

Unit temperature

°

C

T.10

Run status

T.11

Direction

T.12

Warnings

T.13

0-speed*

Table 7-5. Fault time recorded data

* Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred

Real time record

If real time is set to run on the frequency converter the data items T1 and T2 will appear as follows:

T.1

Counted operation days

yyyy-mm-

dd

T.2

Counted operation hours

hh:mm:ss,

s

ss