Vacon nx_6 – mains voltage 525—690 v – TREND NX Variable Speed Drives User Manual

Page 36

Advertising
background image

TECHNICAL DATA

vacon • 19

24-hour support +358 (0)40 837 1150 • Email: [email protected]

4

4.2.2

Vacon NX_6 – Mains voltage 525—690 V

High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min

Following continuous operation at rated output current, 150 % rated output current (IH)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated
output current (IH)

Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 min

Following continuous operation at rated output current, 110% rated output current (IL)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated
output current (IL)


All sizes are available as IP21/NEMA1 or IP54/NEMA12.

Mains voltage 525-690 V, 50/60 Hz, 3~

Loadability

Motor shaft power

Low High

690V

supply

575V supply

Frequency
converter
type

Rated

continuous

current I

L

(A)

10%

overload

current

(A)

Rated

continuous

current I

H

(A)

50%

overload

current

(A)

Max

current

I

S

10%

overload

40°C

P(kW)

50%

overload

50°C

P(kW)

10%

overload

40°C

P(hp)

50%

overload

50°C

P(hp)

Frame

Dimensions and

weight

WxHxD/kg

NX 0004 6

4.5

5.0

3.2

4.8

6.4

3

2.2

3.0

2.0

FR6

195x519x237/18,5

NX 0005 6

5.5

6.1

4.5

6.8

9.0

4

3

3.0

3.0

FR6

195x519x237/18,5

NX 0007 6

7.5

8.3

5.5

8.3

11.0

5.5

4

5.0

3.0

FR6

195x519x237/18,5

NX 0010 6

10

11.0

7.5

11.3

15.0

7.5

5.5

7.5

5.0

FR6

195x519x237/18,5

NX 0013 6

13.5

14.9

10

15.0

20.0

10

7.5

11

7.5

FR6

195x519x237/18,5

NX 0018 6

18

19.8

13.5

20.3

27

15

10

15

11

FR6

195x519x237/18,5

NX 0022 6

22

24.2

18

27.0

36

18.5

15

20

15

FR6

195x519x237/18,5

NX 0027 6

27

29.7

22

33.0

44

22

18.5

25

20

FR6

195x519x237/18,5

NX 0034 6

34

37

27

41

54

30

22

30

25

FR6

195x519x237/18,5

NX 0041 6

41

45

34

51

68

37.5

30

40

30

FR7 237x591x257/35

NX 0052 6

52

57

41

62

82

45

37.5

50

40

FR7 237x591x257/35

NX 0062 6

62

68

52

78

104

55

45

60

50

FR8

291x758x344/58

NX 0080 6

80

88

62

93

124

75

55

75

60

FR8

291x758x344/58

NX 0100 6

100

110

80

120

160

90

75

100

75

FR8

291x758x344/58

NX 0125 6

125

138

100

150

200

110

90

125

100

FR9

480x1150x362/146

NX 0144 6

144

158

125

188

213

132

110

150

125

FR9

480x1150x362/146

NX 0170 6

170

187

144

216

245

160

132

150

150

FR9

480x1150x362/146

NX 0208 6

208

229

170

255

289

200

160

200

150

FR9

480x1150x362/146

NX 0261 6

261

287

208

312

375

250

200

250

200

FR10

595x2018x602/300

NX 0325 6

325

358

261

392

470

315

250

300

250

FR10

595x2018x602/300

NX 0385 6

385

424

325

488

585

355

315

400

300

FR10

595x2018x602/300

NX 0416 6

416

458

325

488

585

400

315

450

300

FR10

595x2018x602/300

NX 0460 6

460

506

385

578

693

450

355

450

400

FR11 794x2018x602/370

NX 0502 6

502

552

460

690

828

500

450

500

450

FR11 794x2018x602/370

NX 0590 6

590

649

502

753

904

560

500

600

500

FR11 794x2018x602/370

NX 0650 6

650

715

590

885

1062

630

560

650

600

FR12

1210x2017x602/600

NX 0750 6

750

825

650

975

1170

710

630

800

650

FR12

1210x2017x602/600

NX 0820 6

820

902

650

975

1170

800

630

800

650

FR12

1210x2017x602/600

Table 4-2. Power ratings and dimensions of Vacon NX, supply voltage 525—690V.

Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is
equal to or less than the factory default.

Note: The rated currents for FR10 to FR12 are all valid at an ambient temperature of 40 °C.

Advertising