Power ratings, Vacon nx_5 – mains voltage 380—500 v – TREND NX Variable Speed Drives User Manual

Page 35

Advertising
background image

18 • vacon

TECHNICAL DATA

Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205

4

4.2 Power

ratings

4.2.1

Vacon NX_5 – Mains voltage 380—500 V

High overload = Max current IS, 2 sec/20 sec, 150% overloadability, 1 min/10 min

Following continuous operation at rated output current, 150 % rated output current (IH)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated
output current (IH)

Low overload = Max current IS, 2 sec/20 sec, 110% overloadability, 1 min/10 min

Following continuous operation at rated output current, 110% rated output current (IL)
for 1 min, followed by a period of load current less than rated current, and of such
duration that the r.m.s output current, over the duty cycle, does not exceed rated
output current (IL)

All sizes are available as IP21/NEMA1. Sizes FR4 to FR9 are additionally available as IP54/NEMA12.

Mains voltage 380-500 V, 50/60 Hz, 3~

Loadability

Motor shaft power

Low

High

380V supply

500V supply

Frequency
converter
type

Rated

continuous

current I

L

(A)

10%

overload

current

(A)

Rated

continuous

current I

H

(A)

50%

overload

current

(A)

Max

current

I

S

10%

overload

40°C

P(kW)

50%

overload

50°C

P(kW)

10%

overload

40°C

P(kW)

50%

overload

50°C

P(kW)

Frame

Dimensions and

weight

WxHxD/kg

NX 0003 5

3.3

3.6

2.2

3.3

4.4

1.1

0.75

1.5

1.1

FR4

128x292x190/5

NX 0004 5

4.3

4.7

3.3

5.0

6.2

1.5

1.1

2.2

1.5

FR4

128x292x190/5

NX 0005 5

5.6

6.2

4.3

6.5

8.6

2.2

1.5

3

2.2

FR4

128x292x190/5

NX 0007 5

7.6

8.4

5.6

8.4

10.8

3

2.2

4

3

FR4

128x292x190/5

NX 0009 5

9

9.9

7.6

11.4

14

4

3

5.5

4

FR4

128x292x190/5

NX 0012 5

12

13.2

9

13.5

18

5.5

4

7.5

5.5

FR4

128x292x190/5

NX

0016

5 16 17.6 12 18.0

24 7.5 5.5 11 7.5 FR5 144x391x214/8.1

NX 0022 5

23

25.3

16

24.0

32

11

7.5

15

11

FR5

144x391x214/8.1

NX 0031 5

31

34

23

35

46

15

11

18.5

15

FR5

144x391x214/8.1

NX 0038 5

38

42

31

47

62

18.5

15

22

18.5

FR6

195x519x237/18.5

NX 0045 5

46

51

38

57

76

22

18.5

30

22

FR6

195x519x237/18.5

NX 0061 5

61

67

46

69

92

30

22

37

30

FR6

195x519x237/18.5

NX 0072 5

72

79

61

92

122

37

30

45

37

FR7

237x591x257/35

NX 0087 5

87

96

72

108

144

45

37

55

45

FR7

237x591x257/35

NX 0105 5

105

116

87

131

174

55

45

75

55

FR7

237x591x257/35

NX 0140 5

140

154

105

158

210

75

55

90

75

FR8

291x758x344/58

NX 0168 5

170

187

140

210

280

90

75

110

90

FR8

291x758x344/58

NX 0205 5

205

226

170

255

336

110

90

132

110

FR8

291x758x344/58

NX 0261 5

261

287

205

308

349

132

110

160

132

FR9

480x1150x362/146

NX 0300 5

300

330

245

368

444

160

132

200

160

FR9

480x1150x362/146

NX 0385 5

385

424

300

450

540

200

160

250

200

FR10

595x2018x602/300

NX 0460 5

460

506

385

578

693

250

200

315

250

FR10

595x2018x602/300

NX 0520 5

520

572

460

690

828

250

250

355

315

FR10

595x2018x602/300

NX 0590 5

590

649

520

780

936

315

250

400

355

FR11

794x2018x602/370

NX 0650 5

650

715

590

885

1062

355

315

450

400

FR11

794x2018x602/370

NX 0730 5

730

803

650

975

1170

400

355

500

450

FR11

794x2018x602/370

NX 0820 5

820

902

730

1095

1314

450

400

500

500

FR12

1210x2017x602/600

NX 0920 5

920

1012

820

1230

1476

500

450

630

500

FR12

1210x2017x602/600

NX 1030 5

1030

1133

920

1380

1656

500

500

710

630

FR12

1210x2017x602/600

Table 4-1. Power ratings and dimensions of Vacon NX, supply voltage 380—500V.

Note: The rated currents in given ambient temperatures are achieved only when the switching frequency is equal to
or less than the factory default.
Note: The rated currents for FR10 to FR12 are all valid at an ambient temperature of 40 °C.

Advertising