NOTE! There are some special functions that can be performed when in the

M3

menu:

Select the keypad as the active control place by keeping the

start

button pushed

down for 3 seconds when the motor is running. The keypad will become the active
control place and the current frequency reference and direction will be copied to the
keypad.

Select the keypad as the active control place by keeping the

stop

button pushed

down for 3 seconds when the motor is stopped. The keypad will become the active
control place and the current frequency reference and direction will be copied to the
keypad.

Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by keeping the

enter

button pushed down for 3 seconds.

Note that if you are in any other than

M3 menu these functions will not work.

If you are in some other than

M3 menu and try to start the motor by pressing the START button

when the keypad is not selected as the active control place you will get an error message

Keypad

Control NOT ACTIVE.

NOTE 2:

By default, the motor can be stopped at all times by pushing the

stop

button

regardless of the selected control place. This default setting can be inactivated by giving
parameter

Stop Button Activated

(P3.4 or P3.6) (menu M3) the value 0. With this value

given to the parameter, pushing the STOP button stops the motor only when the keypad
has been selected as the active control place.