Active faults menu (m4), Can be seen, see chapter 7.3.4, active, Apter 7.3.4) – TREND NX Variable Speed Drives User Manual

Page 94: Chapter 7.3.4). through, Active faults

Advertising
background image

CONTROL KEYPAD

vacon • 77

24-hour support +358 (0)40 837 1150 • Email: [email protected]

7

7.3.4

Active faults menu (M4)

The

Active faults menu

can be entered from the

Main menu

by pushing the

Menu button right

when the

location indication M4 is visible on the first line of the keypad display.

When a fault brings the frequency converter to a stop, the location indication F1, the fault code, a short
description of the fault and the fault type symbol (see Chapter 7.3.4.1) will appear on the display. In
addition, the indication FAULT or ALARM (see Figure 7-1 or Chapter 7.1.1) is displayed and, in case of a
FAULT, the

red led

on the keypad starts to blink. If several faults occur simultaneously, the list of active

faults can be browsed with the

Browser buttons

.


The memory of active faults can store the maximum of 10 faults in the order of appearance. The display
can be cleared with the

Reset button

and the read-out will return to the same state it was before the fault

trip. The fault remains active until it is cleared with the

Reset button

or with a reset signal from the I/O

terminal or fieldbus.

Note! Remove external Start signal before resetting the fault to prevent unintentional restart of the drive.

Normal state,
no faults:


F0

READY

I/Oterm

Active faults