Dc supply and brake resistor cables, Control cable, Cable and fuse sizes, nx_2 and nx_5, fr4 to fr9 – TREND NX Variable Speed Drives User Manual

Page 59: Table 6-2 an, To fr9), see table 6-2 and table 6-3

Advertising
background image

42 • vacon

CABLING AND CONNECTIONS

Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205

6

4

= Screened cable equipped with compact low-impedance

shield (NKCABLES /JAMAK, SAB/ÖZCuY-O or similar).


Note: The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames).

6.1.1.2

DC supply and brake resistor cables

Vacon frequency converters are equipped with terminals for the DC supply and an optional external brake
resistor. These terminals are marked with B–, B+/R+ and R–. The DC bus connection is made to terminals
B– and B+ and the brake resistor connection to R+ and R–. Note that the DC connection is optional for
drives greater than FR8.

6.1.1.3 Control

cable

For information on control cables see Chapter 6.2.1.1 and Table 6-1.

6.1.1.4

Cable and fuse sizes, NX_2 and NX_5, FR4 to FR9

The table below shows typical cable sizes and types that can be used with the converter. The final selection
should be made according to local regulations, cable installation conditions and cable specification.

Terminal cable size

Frame

Type

I

L

[A]

Fuse

[A]

Mains and

motor cable

Cu [mm

2

]

Main terminal

[mm

2

]

Earth terminal

[mm

2

]

NX0004 2—0008 2
NX0003 5—0009 5

3—8
3—9

10 3*1.5+1.5

1—4

1—2.5

FR4

NX0011 2—0012 2
NX0012 5

11—12

12

16 3*2.5+2.5

1—4

1—2.5

NX0017 2
NX0016 5

17
16

20 3*4+4

1—10

1—10

NX0025 2
NX0022 5

25
22

25 3*6+6

1—10

1—10

FR5

NX0031 2
NX0031 5

32
31

35 3*10+10

1—10

1—10

NX0048 2
NX0038 5—0045 5

48

38—45

50 3*10+10

2.5—50 Cu

6—50 Al

2.5—35

FR6

NX0061 2
NX0061 5

61 63 3*16+16

2.5—50 Cu

6—50 Al

2.5—35

NX0075 2
NX0072 5

75
72

80 3*25+16

2.5—50 Cu

6—50 Al

6—70

NX0088 2
NX0087 5

88
87

100 3*35+16

2.5—50 Cu

6—50 Al

6—70

FR7

NX0114 2
NX0105 5

114
105

125 3*50+25

2.5—50 Cu

6—50 Al

6—70

NX0140 2
NX0140 5

140 160 3*70+35 25—95

Cu/Al 25—95

NX0170 2
NX0168 5

168 200 3*95+50 95—185

Cu/Al 25—95

FR8

NX0205 2
NX0205 5

205 250 3*150+70 95—185

Cu/Al 25—95

NX0261 2
NX0261 5

261 315 3*185+95

or

2*(3*120+70)

95—185 Cu/Al 2

5—95

FR9

NX0300 2
NX0300 5

300

315

2*(3*120+70)

95—185 Cu/Al 2

5—95

Table 6-2. Cable and fuse sizes for Vacon NX_2 and NX_5 (FR4 to FR9)

Advertising